The EL1702 digital input terminal acquires the binary control signals from the process level and transmits them, in an electrically isolated form, to the higher-level automation unit. It is possible to connect 120 V/230 V AC actuators directly. The EtherCAT Terminal contains two channels that indicate their signal state by means of light emitting diodes.
Technical data | EL1702 | ES1702 |
---|---|
Connection technology | 4-wire |
Number of inputs | 2 |
Nominal voltage | 120/230 V AC |
“0“ signal voltage | 0…40 V |
“1“ signal voltage | 79…260 V |
Input current | > 3 mA, typ. 6 mA |
Input filter | typ. 10 ms |
Distributed clocks | – |
Switching times | 10 ms |
Current consumption power contacts | – |
Current consumption E-bus | typ. 110 mA |
Electrical isolation | 500 V (E-bus/mains voltage); 3750 V AC, 1 min. |
Bit width in the process image | 2 inputs |
Configuration | no address or configuration setting |
Weight | approx. 60 g |
Operating/storage temperature | 0…+55 °C/-25…+85 °C |
Relative humidity | 95 %, no condensation |
Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
Protect. class/installation pos. | IP 20/variable |
Pluggable wiring | for all ESxxxx terminals |
![]() |
![]() |
Product announcement |
estimated market release on request |
![]() |
![]() |